Once the connections have been made, choose the desired test voltage on the
rotary switch.
When powered up, the instrument displays the following:
Condition of the battery.
Test voltage.
Voltage present on the object to be tested.
Press the START/STOP button to start the measurement.
During measurements, the instrument will beep every 10 seconds to alert the
user that a high voltage is present.
Press the START/STOP button again to stop the measurement. The
instrument will continue to measure external voltages, but the test result will
remain displayed on the main display unit.
WARNING:
discharge the circuit under test, allow for the voltage displayed to fall
back below 25 V before disconnecting the leads
Before the
measurement
(2 Presses)
During the
measurement
(2 Presses)
After the measurement
(5 Presses)
Megohmmeter Model 6505 - User Manual
To ensure your safety, the instrument will automatically
Press the DISPLAY button to display:
Voltage present on the device to be tested.
Test voltage.
Surface leakage current.
Test voltage.
Instantaneous insulation resistance value.
Duration of the measurement.
Current flowing in the resistance being
measured.
Voltage present on the device tested.
Insulation resistance value just before the
measurement was stopped.
Duration of the measurement.
Test voltage generated during the measurement.
Current that flowed in the resistance measured.
Surface leakage current.
Capacitance.
.