10
TTH200 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH200-EN REV. B
3 Use in potentially explosive atmospheres in accordance with FM and CSA
Change from one to two columns
Note
•
Further information on the approval of devices for use in
potentially explosive atmospheres can be found in the
explosion protection test certificates (at
www.abb.com/temperature).
•
Depending on the design, a specific marking in accordance
with FM or CSA applies.
Ex marking
Transmitter
FM Intrinsically Safe
Model TTH200-L1
Control Drawing
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, AEx ia IIC T6
FM Non-Incendive
Model TTH200-L2
Control Drawing
Class I, Div. 2, Groups A, B, C, D
CSA Intrinsically Safe
Model TTH200-R1
Control Drawing
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, Ex ia Group IIC T6
CSA Non-Incendive
Model TTH200-R2
Control Drawing
Class I, Div. 2, Groups A, B, C, D
TTH200-L1H (I.S.)
TTH200-L2H (N.I.)
TTH200-R1H (I.S.)
TTH200-R2H (1) (N.I.)
TTH200-R2H (2, no conduit) (N.I.)
LCD indicator
FM Intrinsically Safe
Control Drawing
I.S. Class I Div 1 and Div 2, Group: A, B, C, D or
I.S. Class I Zone 0 AEx ia IIC T*
U
/ V
= 9 V, I
/ I
< 65.2 mA, P
i
max
i
max
FM Non-Incendive
Control Drawing
N.I. Class I Div 2, Group: A, B, C, D oder Ex nL IIC T**, Class I Zone 2
U
/ V
= 9 V, I
/ I
< 65.2 mA, P
i
max
i
max
CSA Intrinsically Safe
Control Drawing
I.S. Class I Div 1 and Div 2; Group: A, B, C, D or
I.S Zone 0 Ex ia IIC T*
U
/ V
= 9 V, I
/ I
< 65.2 mA, P
i
max
i
max
CSA Non-Incendive
Control Drawing
N.I. Class I Div 2, Group: A, B, C, D oder Ex nL IIC T**, Class I Zone 2
U
/ V
= 9 V, I
/ I
< 65.2 mA, P
i
max
i
max
*
Temp. Ident: T6 T
56 °C, T4 T
amb
** Temp. Ident: T6 T
60 °C, T4 T
amb
Installation instructions
FM / CSA
The installation, commissioning, maintenance and repair of
devices in areas with explosion hazard must only be carried out
by appropriately trained personnel.
The operator must strictly observe the applicable national
regulations with regard to installation, function tests, repairs,
and maintenance of electrical devices. (e. g. NEC, CEC).
IP protection rating of housing
The temperature transmitter and LCD display type AS must be
installed such that the IP rating of at least IP20 is achieved in
accordance with IEC 60529.
SAP_214 748
= 101 mW, C
= 0.4 μF, L
= 0
i
i
i
SAP_214 751
= 101 mW, C
= 0.4 μF, L
= 0
i
i
i
SAP_214 749
= 101 mW, C
< 0.4 μF, L
= 0
i
i
i
SAP_214 750
= 101 mW, C
< 0.4 μF, L
= 0
i
i
i
85 °C
amb
85 °C
amb