Spark Monitor (Ac Current Transducer) - Watts AERCO Benchmark BMK 1500DF User Manual

Natural gas, propane gas, or dual fuel fired modulating, condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Operation, Service & Maintenance Guide-Latin America
SECTION 4 – MAINTENANCE

4.12 SPARK MONITOR (AC CURRENT TRANSDUCER)

The spark monitor
(P/N 61034)
transformer and igniter-injector. Wire# 140, connected to the ignition transformer (see Figure 4-
12), passes through the monitor's orifice. If an adequate AC current is not detected in the wire
during ignition, the unit automatically shuts down. The monitor's wires are connected to the
board's Spark Signal terminals (see section 2.11.4 in the
and Startup Guide, OMM-0131 (GF-205-LA) for details ).
Spark
Monitor
To I/O
Tab
Board
Figure 4-12: Spark Detector Sensor (AC Current Transducer) P/N 61034
If the spark monitor needs to be replaced, open the monitor's orifice by pulling on the tab at
the side, remove Wire# 140, disconnect the monitor's wires are from the I/O board, r e m o v e
the old monitor from its position, i n s t a l l a new monitor in its place, r o u t e wire# 140
through the new sensor orifice, and connect the wires to the I/O board's Spark Signal
terminals, red wire to the positive (+) terminal and black to negative (-).
Page 56 of 162
01/02/2018
evaluates the strength of the current between the ignition
Wire 140
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Benchmark 750 – 3000 Installation
Ignition
Transformer
I/O
Wire 140
OMM-0132_A
GF-206-LA-LA

Advertisement

Table of Contents
loading