Bmk 2500/3000 Combustion Cal Menus - Watts AERCO Benchmark BMK 1500DF User Manual

Natural gas, propane gas, or dual fuel fired modulating, condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Operation, Service & Maintenance Guide-Latin America
SECTION 2: OPERATION

2.8.3 BMK 2500/3000 COMBUSTION CAL Menus

TABLE 2-8a: COMBUSTION CAL Menu: BMK 2500/3000
SINGLE FUEL – NATURAL GAS
MENU ITEM DISPLAY
CAL Voltage 16%
1
CAL Voltage 14%
2
CAL Voltage 30%
3
CAL Voltage 40%
4
CAL Voltage 50%
5
CAL Voltage 70%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
TABLE 2-8b: COMBUSTION CAL Menu: BMK 2500/3000
MENU ITEM DISPLAY
CAL Voltage: 14%
CAL Voltage: 16%
1
CAL Voltage: 18%
CAL Voltage: 20%
CAL Voltage: 22%
2
CAL Voltage 30%
3
CAL Voltage 45%
4
CAL Voltage 65%
CAL Voltage 70%
5
CAL Voltage 75%
CAL Voltage 85%
6
CAL Voltage 100%
7
SET Valve Position
8
Blower Output
9
Set Stdby Volt
10
Oxygen Level
* The default values for Natural Gas on Dual Fuel units are different than the default values for
Natural Gas on Single Fuel units. These values shown DO NOT APPLY to single fuel units.
OMM-0132A
GF-206-LA-LA
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0%
100%
0
10.00 V
MINIMUM
MAXIMUM
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0.25
10.00
0
100
0
10.0
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
DEFAULT
BMK 2500
2.20
4.10
4.80
5.30
6.80
8.50
Variable
Displays current value
2.00 V
Displays current value
DEFAULT
*
NATURAL GAS
BMK 2500
BMK 3000
2.40
2.15
2.10
5.40
3.90
6.60
5.60
7.00
6.60
8.00
8.70
8.50
Displays current value
2.00
2.00
Displays current value
BMK 3000
2.80
4.60
5.00
5.50
6.90
9.10
2.00 V
DUAL FUEL
PROPANE
BMK 2500
BMK 3000
2.00
2.30
2.00
3.30
4.40
4.60
5.40
5.70
5.60
7.00
7.90
8.60
Variable
2.00
2.00
Page 23 of 162
01/02/2018

Advertisement

Table of Contents
loading

Table of Contents