Watts AERCO Benchmark BMK 1500DF User Manual page 40

Natural gas, propane gas, or dual fuel fired modulating, condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Operation, Service & Maintenance Guide-Latin America
SECTION 4 – MAINTENANCE
The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to
remove the igniter-injector from the unit after the unit has cooled to room temperature. To
inspect/replace the Igniter:
Igniter-Injector Maintenance Procedure Instructions
1. Set the ON/OFF switch on the C-More Controller to the OFF position. Disconnect AC
power from the unit
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up. This
will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the cable from the igniter-injector (see Figure 4-1a – Figure 4-1c, above).
4. Referring to Figure 4-2a – Figure 4-2c, below, use a 7/16" open-end wrench to disconnect
the compression nut securing the gas injector tube of the igniter-injector to the elbow of the
staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector.
FLAME
DETECTOR
& GASKET
BURNER
PLATE
LEAN O
SENSOR
2
& WASHER
Figure 4-2a: BMK 750/1000 Igniter-Injector & Flame Detector Mounting Details
STAGED
IGNITION
SOLENOID
INJECTOR-IGNITER
ASSY WITH INDEXING
(CLOCKING) WASHERS
(0-3 as needed)
LEAN O2 SENSOR
& WASHER
BURNER PLATE
FLANGE
Figure 4-2b: BMK 1500/2000 Igniter-Injector & Flame Detector Mounting Details
Page 40 of 162
01/02/2018
COMPRESSION
FITTING & ELBOW
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
STAGED
IGNITION
SOLENOID
IGNITER-INJECTOR
INDEXING
(CLOCKING)
WASHERS
(0-3 as required)
BLOWER
PLENUM
FLAME
OBSERVATION
PORT
FLAME
DETECTOR &
GASKET
OMM-0132_A
GF-206-LA-LA

Advertisement

Table of Contents
loading

Table of Contents