6.5 Setting up the energy metering
6.5.1 Produced heat
6.5.2 Consumed energy
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
▪
If the applicable legislation requires a higher temperature than the maximum
tank setpoint during disinfection (see [2-03] in the field settings table), you can
connect a DHW pump and heater element as shown above.
▪
If applicable legislation requires disinfection of the water piping until the tapping
point, you can connect a DHW pump and heater element (if needed) as shown
above.
▪
To ensure a complete disinfection, you have to open the tapping point.
WARNING
When opening the tapping point, the water temperature can be up to 55°C.
Configuration
The indoor unit can control DHW pump operation. For more information, see
4
"10 Configuration" [
110].
▪
Via the user interface, you can read out the following energy data:
-
Produced heat
-
Consumed energy
▪
You can read out the energy data:
-
For space heating
-
For space cooling
-
For domestic hot water production
▪
You can read out the energy data:
-
Per month
-
Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
▪
The produced heat is calculated internally based on:
-
The leaving and entering water temperature
-
The flow rate
▪
Setup and configuration: No additional equipment needed.
You can use the following methods to determine the consumed energy:
▪
Calculating
6
Application guidelines
|
Installer reference guide
41