Daikin EHFZ03S18DJ3V Installer's Reference Manual page 36

Hide thumbs Also See for EHFZ03S18DJ3V:
Table of Contents

Advertisement

6
|
Application guidelines
Installer reference guide
36
INFORMATION
During heating operation of the heat pump, the heat pump operates to achieve
the desired temperature set via the user interface. When weather-dependent
operation is active, the water temperature is determined automatically
depending on the outdoor temperature.
During heating operation of the auxiliary boiler, the auxiliary boiler operates to
achieve the desired water temperature set via the auxiliary boiler controller.
Setup
Integrate the auxiliary boiler as follows:
A Main leaving water temperature zone
B One single room
a User interface used as room thermostat
b Non-return valve (field supply)
c Shut-off valve (field supply)
d Auxiliary boiler (field supply)
e Aquastat valve (field supply)
f Bypass (field supply)
NOTICE
Make sure the auxiliary boiler and its integration in the system complies with
applicable legislation.
Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler
system.
Make sure the return water to the heat pump does NOT exceed 60°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
-
Install an aquastat valve in the return water flow of the heat  pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
Install non-return valves.
An expansion vessel is already pre-mounted in the indoor unit. But for bivalent
operation, also make sure that there is an expansion vessel in the auxiliary boiler
loop. Otherwise when bivalent operation is running and if the Aquastat valve
would close, there would be no expansion vessel in the water circuit anymore.
Install the digital I/O PCB (option EKRP1HBAA).
Connect X1 and X2 (changeover to external heat source) on the digital I/O PCB to
the auxiliary boiler. See
4
source" [
 104].
b
b
c
d
c
f
e
A
"9.3.9  To connect the changeover to external heat
B
a
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma 3 r fErla03dav3Erla-dvEhfz-d3v

Table of Contents