Daikin EHFZ03S18DJ3V Installer's Reference Manual page 125

Hide thumbs Also See for EHFZ03S18DJ3V:
Table of Contents

Advertisement

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
#
[A.3.1.3.1]
[1-0B]
[A.3.1.3.2]
[1-0D]
Leaving water temperature: Modulation
To allow better matching of the heat  pump capacity with the actual required
capacity, enable the leaving water temperature modulation. If modulation is
enabled, the unit calculates the leaving water temperature according to the
difference between desired and actual room temperature. As a result, the
heat pump will have less start/stop cycles and thus operate more economical.
If modulation is enabled, you can also set the maximum modulation of the leaving
water temperature. The maximum modulation is the value by which the desired
leaving water temperature is increased or lowered.
#
[A.3.1.1.5]
[8-05]
N/A
[8-06]
INFORMATION
When leaving water temperature modulation is enabled, the weather‑dependent
curve needs to be set to a higher position than [8-06] plus the minimum leaving
water temperature setpoint required to reach a stable condition on the comfort
setpoint for the room. To increase efficiency, modulation can lower the leaving water
setpoint. By setting the weather‑dependent curve to a higher position, it cannot drop
below the minimum setpoint. See the illustration below.
T t
+[8-06]
−[8-06]
a Weather-dependent curve
b Minimum leaving water temperature setpoint required to reach a stable condition
on the comfort setpoint for the room.
T
Target leaving water temperature
t
T
Outdoor temperature
a
Leaving water temperature: Emitter type
Heating up or cooling down the main zone can take longer. This depends on:
The water volume of the system
The heater emitter type of the main zone
Code
Delta T for heating
Range: 3°C~10°C
Delta T for cooling
Range: 3°C~10°C
Code
Modulated LWT:
0 (No): Disabled
1 (Yes): Enabled
Maximum modulation:
Range: 0°C~10°C
a
b
T a
10
Configuration
|
Description
Description
Installer reference guide
125