Daikin EHFZ03S18DJ3V Installer's Reference Manual page 206

Hide thumbs Also See for EHFZ03S18DJ3V:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
└─ Space operation
└─ LWT settings
└────────────────── Main
A.3.1.1.1
LWT setpoint mode
A.3.1.1.2.1
[9-01]
Temperature range
A.3.1.1.2.2
[9-00]
Temperature range
A.3.1.1.2.3
[9-03]
Temperature range
A.3.1.1.2.4
[9-02]
Temperature range
A.3.1.1.5
[8-05]
Modulated LWT
A.3.1.1.7
[2-0C]
Emitter type
└────────────────── Additional
A.3.1.2.1
LWT setpoint mode
A.3.1.2.2.1
[9-05]
Temperature range
A.3.1.2.2.2
[9-06]
Temperature range
A.3.1.2.2.3
[9-07]
Temperature range
A.3.1.2.2.4
[9-08]
Temperature range
└────────────────── Delta T source
A.3.1.3.1
[1-0B]
Delta T heating
A.3.1.3.2
[1-0D]
Delta T cooling
└─ Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
A.3.2.1.2
[3-06]
Room temp. range
A.3.2.1.3
[3-09]
Room temp. range
A.3.2.1.4
[3-08]
Room temp. range
A.3.2.2
[2-0A]
Room temp. offset
A.3.2.4
Room temp. step
└─ Operation range
A.3.3.1
[4-02]
Space heating OFF temp
A.3.3.2
[F-01]
Space Cooling ON temp
└─ Domestic hot water (DHW)
└─ Type
A.4.1
[6-0D]
└─ Disinfection
A.4.4.1
[2-01]
Disinfection
A.4.4.2
[2-00]
Operation day
A.4.4.3
[2-02]
Start time
A.4.4.4
[2-03]
Temperature target
A.4.4.5
[2-04]
Duration
└─ Maximum setpoint
A.4.5
[6-0E]
└─ SP mode
A.4.6
└─ Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
A.4.7
[0-0C]
Weather-dependent curve
A.4.7
[0-0D]
Weather-dependent curve
A.4.7
[0-0E]
Weather-dependent curve
└─ Heat sources
└─ Backup heater
A.5.1.4
[5-01]
Equilibrium temp.
A.5.1.5
[8-0E]
BUH only ambient temp.
└─ System operation
└─ Auto restart
A.6.1
[3-00]
(*1) Only applicable for models where cooling is possible
(*2) EHFZ03S18DJ3V
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
Minimum temp (heating)
Maximum temp (heating)
Minimum temp (cooling)
Maximum temp (cooling)
DHW setpoint for high ambient temp. for DHW
WD curve.
DHW setpoint for low ambient temp. for DHW
WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Range, step
Default value
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~60°C, step: 1°C
55°C
R/W
5~18°C, step: 1°C
5°C
R/W
18~22°C, step: 1°C
22°C
R/W
0: No
1: Yes
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
R/W
15~37°C, step: 1°C
25°C
R/W
37~60°C, step: 1°C
55°C
R/W
5~18°C, step: 1°C
5°C
R/W
18~22°C, step: 1°C
22°C
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
12~18°C, step: A.3.2.4
12°C
R/W
18~30°C, step: A.3.2.4
30°C
R/W
15~25°C, step: A.3.2.4
15°C
R/W
25~35°C, step: A.3.2.4
35°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: 1°C
1: 0,5°C
R/W
14~35°C, step: 1°C
22°C
R/W
10~35°C, step: 1°C
20°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
0: No
1: Yes
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0~23 hour, step: 1 hour
1
R/W
fixed value
60°C
R/W
40~60 min, step: 5 min
40 min
R/W
40~60°C, step: 1°C
60°C
R/W
0: Fixed
1: Weather dep.
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
60°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-15~35°C, step: 1°C
0°C
R/W
-15~-7°C, step: 1°C
-7°C
R/W
0: No
1: Yes
3/7
Installer setting at variance with
default value
Date
Value
4P596829-1A - 2021.10