10
|
Configuration
Installer reference guide
124
Leaving water temperature: Additional zone
#
[A.3.1.2.1]
N/A
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
[7.7.2.2]
[0-04]
[0-05]
[0-06]
[0-07]
(a)
Also see
"10.3 Weather-dependent
Leaving water temperature: Delta T source
The Delta T is the required temperature difference between entering and leaving
water. This applies to both temperature zones. Change the value of Delta T if
another minimum temperature difference is required for the good operation of the
heat emitters in heating or cooling mode.
Code
Select the setpoint mode of the leaving water
temperature.
LWT setpoint mode:
▪
0 (Fixed): Absolute
▪
1 (Weather dep.): Weather-dependent
▪
2
(Fixed/scheduled):
scheduled
method=LWT control)
▪
3 (WD/scheduled): Weather-dependent +
scheduled
method=LWT control)
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent heating:
T t
[0-01]
[0-00]
[0-03]
▪
T
:
Target
t
(additional)
▪
T
: Outdoor temperature
a
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent cooling:
T t
[0-05]
[0-04]
[0-07]
▪
T
:
Target
t
(additional)
▪
T
: Outdoor temperature
a
curve" [
4
127].
Description
Absolute
(only
if
Unit
(only
if
Unit
[0-02]
T a
leaving
water
temperature
[0-06]
T a
leaving
water
temperature
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10
+
control
control