Disposal; Overview: Disposal; To Pump Down - Daikin EHFZ03S18DJ3V Installer's Reference Manual

Hide thumbs Also See for EHFZ03S18DJ3V:
Table of Contents

Advertisement

15
|

Disposal

15 Disposal
In this chapter

15.1 Overview: Disposal

15.2 To pump down

Installer reference guide
190
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
15.1
Overview: Disposal ................................................................................................................................................................. 190
15.2
To pump down........................................................................................................................................................................ 190
Typical workflow
Disposing of the system typically consists of the following stages:
1
Pumping down the system.
2
Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
NOTICE
During pump down operation, stop the compressor before removing the refrigerant
piping. If the compressor is still running and the stop valve is open during pump
down, air will be sucked into the system. Compressor breakdown or damage to the
system can result due to abnormal pressure in the refrigerant cycle.
NOTICE
Before pump down. Before using the unit's automatic pump down function, do the
following settings:
Set [C-07]=0 (or [A.2.1.7]:
Standard > Unit control method = LWT control)
Set [7-02]=1 (or [A.2.1.8]:
Standard > Number of LWT zones = 2 LWT zones)
> Installer settings > System layout >
> Installer settings > System layout >
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma 3 r fErla03dav3Erla-dvEhfz-d3v

Table of Contents