Product Description; Introduction; Scope Of Delivery; Proper Use - Riello Array AR 2000 Installation And Operation Manual

Table of Contents

Advertisement

PRODUCT DESCRIPTION

2 PRODUCT DESCRIPTION

2.1 Introduction

• The gas-fired condensing Array boilers are designed to be used
in central heating systems. Any other use is prohibited.
• This boiler can be connected to an indirect storage tank for the
production of domestic hot water.
• There are several options available for venting. See section "4.15
Venting" for details.
• The quality of the system water is very important. Poor water
quality can damage heating systems and boilers due to scale
formation and corrosion (section "4.6 Water quality guidelines").
• The boilers can also function directly with any hydronic emitter.
When installing the boiler and system connections, the installer
must consider the total head loss and flow rates in order to
adequately size piping and circulator pumps.
• The Array boiler can be connected to a room thermostat or by
a 0-10V input.
• An outdoor air temperature sensor must be connected to the
boiler for an outdoor reset supply temperature control for
increased fuel efficiency and comfort.

2.2 Scope of delivery

2
3
4
5
6
7
8
Scope of delivery
Fig. 1
Component
1
Gas condensing boiler
2
Set of documents for
appliance
3
Cabinet Keys
4
System sensor
5
Outdoor sensor
6
Adapter for condensate
drain system (1" PVC
female)
7
Adapter for relief valves
drain system (2.5" NPT
female)
1
10
9
Qty
Packaging method
1
Pallet
1
Plastic package
1
Cardboard box in boiler
1
Cardboard box in boiler
1
Cardboard box in boiler
1
Cardboard box in boiler
1
Cardboard box on pallet
Component
8
Anchoring brackets
9
Thermowell for System
Temperature Sensor
10 Gas filter

2.3 Proper Use

► The Array boilers are designed for large residential, commercial
and industrial applications.
► The Array boilers are delivered in compliance with CSD-1
Commercial applications.
► The appliance may only be installed in closed loop hot water
central heating systems.
► Any other purpose is considered improper use. Any resulting
damage is excluded from the manufacturer's warranty.
► In some heating applications like pool, spa or process water
heating, a heat exchanger must be installed

2.4 Environmental Responsibility / Disposal

Environmental responsibility is one of the fundamental company
policies of the
Group.
R
We regard quality of performance, economy and environmental
responsibility as equal objectives. Environmental protection laws
and regulations are strictly adhered to.
To protect the environment, we use the best possible technology
and materials while also taking into account economic points of
view.
Packaging
All packaging materials used are environmentally-friendly and
recyclable.

2.5 Emergency Shutdown

If overheating occurs or the gas supply fails to shut off, close the
manual gas shutoff valve (Fig. 2) located external to the unit.
NOTE: The Installer must identify and indicate the location of the
manual emergency shutoff valve.
Fig. 2
Manual Gas Shutoff Valve
6
Qty
Packaging method
4
Cardboard box on pallet
1
Cardboard box on pallet
1
Cardboard box on pallet

Hide quick links: