Max operating temperature
Max HE allowable temperature
Ambient storage temperature
Ambient functioning temperature
Max Ambient Functioning Humidity
Surface heat exchanger per module
Standard Listings & Approvals
Electrical Req.
Weight (dry)
Dimension W x H x D
(**) FLA (Full Load Amperage) – maximum current drawn by the boiler if all pumps reach rated horsepower
(***) Mounting feet may be removed during installation to reduce the overall height by 2". Feet must be re-installed once boiler is in
its final installation location.
Unit
AR 1000
°F
194
(°C)
(90)
°F
210
(°C)
(98.9)
°F
5 to 158
(°C)
(-15 to 70)
°F
32 to 120
(°C)
(0 to 49)
°F
95 % at 104
(°C)
95 % at 40
SQFT
43
(m
)
(4)
2
120V/1Ph/60Hz / 15.5 FLA**
lbs
1058
(kg)
(480)
Inch
33.3X67.2X60.8 ***
(mm)
(845X1707X1544)
11
AR 1500
194
(90)
210
(98.9)
5 to 158
(-15 to 70)
32 to 120
(0 to 49)
95 % at 104
95 % at 40
43
(4)
ETL, ASME, AHRI, CSD-1, SCAQMD
120V/1Ph/60Hz / 23.3 FLA**
1323
(600)
33.3X67.2X60.8 ***
(845X1707X1544)
PRODUCT DESCRIPTION
AR 2000
194
(90)
210
(98.9)
5 to 158
(-15 to 70)
32 to 120
(0 to 49)
95 % at 104
95 % at 40
43
(4)
230V/1Ph/60Hz / 15.5 FLA**
1676
(760)
33.3X83X60.8 ***
845X2108X1544)