MONITORING SOLUTION ENERGY
TEST OF RELAY
TEST OF THE TEMPERATURE SENSORS
For each enabled temperature sensor, the system will check the sensor and return temperature with
one of the following test result icons:
: The sensor is correctly interrogated.
: The system failed to interrogate the sensor.
: The sensor is being evaluated.
TEST OF THE PARTIAL DISCHARGE PROBES
AMS01 partial discharge detection system use specific filters to monitor partial discharge. In system
test mode, you can select the configuration of this filter depending on your method to generate partial
discharge. An incorrect selection will result in no detection of partial discharge.
Possible configuration for AMS01 system:
-
Use the reader actual settings (50 Hz or 60 Hz).
-
Use of OMICRON generator configured on 50 Hz.
-
Use of OMICRON generator configured on 60 Hz.
-
Use of a non-conventional generator, in this case filters are totally deactivated and
external noise could perturbate calculation of PD values.
For each enabled PD probe, the system will evaluate the partial discharge levels (based on default
values of PD notifiers) and the 'PD Indicator' icon can take one of the following values:
: The system has detected no partial discharge activity.
: The system has detected low partial discharge activity.
: The system has detected a medium partial discharge activity.
: The system has detected a high partial discharge activity.
AMS01 Configuration Tool User Manual
www.senseor.com
: When the test is running, click on the toggle button to open/close the relay.
: Choose the corresponding test method.
27/29