1MRK506371-UUS Rev. M
During testing, observe that the right testing method, that corresponds to the actual parameters set in the
activated parameter setting group, is used.
Set and configure the function(s) before testing. Most functions are highly flexible and permit a choice of
functional and tripping modes. The various modes are checked at the factory as part of the design
verification. In certain cases, only modes with a high probability of coming into operation need to be
checked when commissioned to verify the configuration and settings.
10.2

Activating the test mode

Put the IED into the test mode before testing. The test mode blocks almost all the protection functions
(except busbar differential protections) and some of the control functions in the IED. The individual
functions to be tested can be unblocked to prevent unwanted operation caused by other functions. In this
way, it is possible to test slower back-up measuring functions without the interference from faster
measuring functions. The test switch should then be connected to the IED. Test mode is indicated when
the yellow Pickup LED flashes.
It is important that the IED function to be tested is put into test mode, even if the MU is sending data
marked as "test". The IED will interpret these data as valid if it is not in test mode.
1.
Browse to the TESTMODE menu and press E.
The TESTMODE menu is found on the local HMI under Main menu /Test/IED test mode /
TESTMODE
2.
Use the up and down arrows to choose Enabled and press E.
3.
Press the left arrow to exit the menu.
The dialog box Save changes appears.
4.
Choose Yes, press E and exit the menu.
The yellow pickup LED above the LCD will start flashing when the IED is in test mode.
10.3

Preparing the connection to the test equipment

The IED can be equipped with a test switch of type RTXP8, RTXP18 or RTXP24 or FT. The test switch
and its associated test plug handles are a part of the COMBITEST or FT systemof Hitachi Energy, which
provides secure and convenient testing of the IED.
When using the COMBITEST, preparations for testing are automatically carried out in the proper
sequence, that is, for example, blocking of tripping circuits, short circuiting of CTs, opening of voltage
circuits, making IED terminals available for secondary injection. Terminals 1 and 8, 1 and 18 as well as 1
and 12 of the test switches RTXP8, RTXP18 and RTXP24 respectively are not disconnected as they
supply DC power to the protection IED. When FT switch is used for testing, care shall be exercised to
open the tripping circuit, ahead of manipulating the CT fingers.
The RTXH test-plug handle leads may be connected to any type of test equipment or instrument. When a
number of protection IEDs of the same type are tested, the test-plug handle only needs to be moved from
the test switch of one protection IED to the test switch of the other, without altering the previous
connections.
Line distance protection REL670
Commissioning manual
Parameters can be entered into different setting groups. Make sure to test functions for the
same parameter setting group. If needed, repeat the tests for all different setting groups used.
The difference between testing the first parameter setting group and the remaining is that
there is no need for testing the connections.
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 10
Testing IED operation
M11412-2 v16
M11743-2 v10
77