1MRK506371-UUS Rev. M
Section 14
14.1
Checking the self supervision signals
14.1.1
Checking the self supervision function
14.1.1.1
Determine the cause of an internal failure
This procedure describes how to navigate the menus in order to find the cause of an internal failure when
indicated by the flashing green LED on the HMI module.
Procedure
1.
Display the general diagnostics menu.
Navigate the menus to:
Diagnostics/IED status /General
2.
Scroll the supervision values to identify the reason for the failure.
Use the arrow buttons to scroll between values.
14.1.2
Self supervision HMI data
14.1.2.1
General IED status
The following table shows the general IED status signals.
Table 47:
Indicated result
Internal fail Off
Internal fail On
Internal warning Off
Internal warning On
Time synch Ready
Time synch Fail
Real time clock Ready
Real time clock Fail
ADC-module OK
ADC-module Fail
(Protocol name) Ready
Table continues on next page
Line distance protection REL670
Commissioning manual
Troubleshooting
Signals from the General menu in the diagnostics tree.
Possible reason
No problem detected.
A failure has occurred.
No problem detected.
A warning has been
issued.
No problem detected.
No time synchronization.
No problem detected.
The real time clock has
been reset.
No problem detected.
The AD conversion
module has failed.
No problem detected.
© 2017 - 2023 Hitachi Energy. All rights reserved
Proposed action
None.
Check the rest of the indicated results to find the fault.
None.
Check the rest of the indicated results to find the fault.
None.
Check the synchronization source for problems.
If the problem persists, contact your Hitachi Energy representative
for service.
None.
Set the clock.
None.
Contact your Hitachi Energy representative for service.
None.
Section 14
Troubleshooting
IP1474-1 v2
IP1473-1 v1
M11657-2 v2
IP1472-1 v2
GUID-A84F3903-8A70-47D6-8613-AD7FF8BA3AEC v1
M11656-1 v4