Hitachi Relion 670 Series Commissioning Manual page 150

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
2
1
0
1
0
-1
2
1
0
2
1
0
2
1
0
1
0
-1
0
IEC10000142 V1 EN-US
Figure 42:
11.4.13
Automatic switch onto fault logic ZCVPSOF
Prepare the IED for verification of settings outlined in Section
The automatic switch onto fault logic function ZCVPSOF is checked using secondary injection tests.
ZCVPSOF is activated either by the external input BC or by the internal DLD. FUFSPVC is done with a
pre-fault condition where the phase voltages and currents are at zero. A three-phase fault with zero
impedance and a three-phase fault with an impedance corresponding to the whole line is applied. This
fault shall cause an instantaneous trip and result in a TRIP indication.
11.4.13.1
Function revision history
Document
revision
A
B
C
D
E
F
Table continues on next page
144
COMMON TRIP COMMAND (trip)
TRIPZ1 (tripZone1)
TRIPZ2 (tripZone2)
GENMODE (generatorMode)
MOTMODE (motorMode)
0.5
1
1.5
2
time in seconds
Boolean output signals for the injected current with two components: a 50 Hz current
component and a 49.5 Hz current component
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
© 2017 - 2023 Hitachi Energy. All rights reserved
START (start)
2.5
3
3.5
"Preparing the IED to verify
1MRK506371-UUS Rev. M
4
4.5
5
IEC10000142-1-en.vsd
settings".
GUID-A7F84AD6-F164-491B-B25E-D3BB002E1BDA v4
Line distance protection REL670
Commissioning manual
M13850-2 v9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rel670

Table of Contents