1MRK506371-UUS Rev. M
X1set
ANSI05000368 V2 EN-US
Figure 33:
Table 31:
Test point
1
2
3
4
5
6
7
8
9
10
Table continues on next page
Line distance protection REL670
Commissioning manual
X
2
1
11
10
12
9
8
25% of RFPPZx/2
50% of RFPPZx/2
RFPP/2
Distance protection characteristic with test points for phase-to-phase measurements
Test points for phase-to-phase loops A-B (Ohm/phase)
Reach
Set value
X
X1
set
R
0
X
X1
set
R
R1
set
X
0.8 x X1
set
R
0.8 x R1
+ RFPPZx/2
set
X
0.5 x X1
set
R
0.5 x R1
+ RFPPZx/2
set
X
RFPPZx/2 x tan (LdAngle)
R
RFPPZx/2
X
RLdFwd x tan (LdAngle)
R
RLdFwd
X
0
R
RLdFwd
X
-0.8 x RLdFwd/2 x tan( AngDir)
R
0.8 x RLdFwd/2
X
-0.4 x RLdFwd x tan( AngDir)
R
0.4 x RLdFwd
X
0.5 x X1
set
R
0.5 x X1
/ tan( AngNegRes)
set
© 2017 - 2023 Hitachi Energy. All rights reserved
80%
3
50%
4
5
ArgLd
6
(Ω/phase)
R
7
13
ArgDir
ANSI05000368-2-en.vsdx
Comments
Section 11
Testing functionality by secondary injection
109