Hitachi Relion 670 Series Commissioning Manual page 71

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506371-UUS Rev. M
IEC140000134 V1 EN-US
1.1. Navigate to the Settings tab.
1.2. Force the IP stack to IPv4 by setting the parameter ForceIPv4 to True.
2.
Set the Connection Parameters on PMU Connection Tester for TCP communication according to
the PMU configuration.
IEC140000135 V1 EN-US
2.1. Set Host IP to the PMU IP address configured for the port in use. Here the LANAB:1
2.2. Set Port to the IED's TCP port set in the PMU under parameter C37.118TCPport (4712 is
2.3. Set the Protocol as IEEE C37.118.2-2011.
Line distance protection REL670
Commissioning manual
IPAddress (192.168.1.10) is set.
default). Alternatively, in order to make an IEEE1344 communication, the 1344TCPport
parameter setting can be used (4713 is default).
© 2017 - 2023 Hitachi Energy. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
IEC140000135-1-en.vsd
Section 9
IEC140000134-1-en.vsd
65