Hitachi Relion 670 Series Commissioning Manual page 268

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Troubleshooting
The internal events in this list not only refer to faults in the IED, but also to other activities, such as
change of settings, clearing of disturbance reports, and loss of external time synchronization.
The information can only be retrieved from the Parameter Setting software package. The PC can be
connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 49:
Event message:
INT--FAIL
INT--FAIL
INT--WARNING
INT--WARNING
IOn--Error
IOn--Error
ADMn-Error
ADMn-Error
MIM1-Error
MIM1-Error
INT--RTC
INT--RTC
INT--TSYNC
INT--TSYNC
INT--SETCHGD
DRPC-CLEARED
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on the:
Module that should be changed.
Sequence of faults, if more than one unit is faulty.
Exact time when the fault occurred.
14.2.3
Diagnosing the IED status via the LHMI hint menu
In order to help the user, there is an LHMI page labeled 'Hints'. This page is located under Main menu/
Diagnostics/IED status/Hints. For each activated hint there is a headline. From the headline view, an
explanation page can be entered, giving the user more information and hints about the particular topic.
For example, if there is a configuration to use IEC 61850 9–2 analog data, but no data arrives on the
access point, then the IED will use substituted data and most protection functions will be blocked. This
condition will be indicated with a sub-menu under Hints, where details about this condition are shown.
The Hint menu is a way to assist the user in troubleshooting.
262
Events available for the internal event list in the IED
Description
Off
Internal fail status
Off
Internal warning status
Off
In/Out module No. n status
Off
Analog/Digital module No. n
status
Off
mA-input module status
Off
Real Time Clock (RTC) status
Off
External time synchronization
status
Any settings in IED changed
All disturbances in Disturbance
report cleared
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK506371-UUS Rev. M
Generating signal:
INT--FAIL (reset event)
INT--FAIL (set event)
lNT--WARNING (reset event)
lNT--WARNING (set event)
IOn--Error (reset event)
IOn--Error (set event)
ADMn-Error (reset event)
ADMn-Error (set event)
MIM1-Error (reset event)
MIM1-Error (set event)
INT--RTC (reset event)
INT--RTC (set event)
INT--TSYNC (reset event)
INT--TSYNC (set event)
GUID-7E8503E9-441B-487A-9CD7-B43463D1CAE5 v6
Line distance protection REL670
Commissioning manual