Section 8
Commissioning
128
A071168 V4 EN
Figure 94:
Selecting the setting group value
Only values within the selected setting group can be changed.
7.
Press
or
to change the value and
A070922 V4 EN
Figure 95:
Editing the setting group value
The active setting group is indicated with an asterisk * .
Switching the Operation parameter of a function block on or off
restarts all control and protection functions.
Activating a setting group
Protection relay settings are planned in advance for different operation conditions by
calculating setting values to different setting groups. The active setting group can be
changed by the protection relay application or manually from the menu.
1.
Select Main menu/Settings/Setting group/Active group and press
1MRS758754 B
to confirm the selection.
REC615 and RER615
Operation Manual
.