Communication - ABB RELION REC615 Operation Manual

Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758754 B
3.5
REC615 and RER615
Operation Manual
Table 17:
Comparison of authority logging levels
Audit trail event
None
Configuration change
Firmware change
Firmware change fail
Attached to retrofit test
case
Removed from retrofit
test case
Setting group remote
Setting group local
Control remote
Control local
Test on
Test off
Reset trips
Setting commit
Time change
View audit log
Login
Logout
Password change
Firmware reset
Violation local
Violation remote

Communication

Operational information and controls are available through these protocols. However,
some communication functionality, for example, horizontal communication between
the protection relays, is only enabled by the IEC 61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings, disturbance recordings and fault records
can be accessed using the IEC 61850 protocol. Disturbance recordings are available
to any Ethernet-based application in the IEC 60255-24 standard COMTRADE file
format. The protection relay can send and receive binary signals from other devices
(so-called horizontal communication) using the IEC 61850-8-1 GOOSE profile,
where the highest performance class with a total transmission time of 3 ms is
supported. Furthermore, the protection relay supports sending and receiving of analog
REC615 and RER615 overview
Authority logging level
Configurati
Setting
Setting
on change
group
group,
control
Section 3
Settings
All
edit
33