Controlling With The Closing Delay - ABB RELION REC615 Operation Manual

Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758754 B
6.2.3
REC615 and RER615
Operation Manual
A071172 V3 EN
Figure 77:
The time between selecting the object and giving a control command
is restricted by an adjustable time-out. When an object is selected, the
control command has to be given within this time.
With default configurations it is possible to control a breaker open
even when the breaker is in an intermediate state.

Controlling with the closing delay

Close delay mode and Close delay need to be set to be able to control objects with the
closing delay.
The closing operation from the LHMI can be delayed by a predefined period of time.
1.
Press
to close the selected object.
If there are several controllable objects, select the object and press
confirm the selection.
2.
To confirm the operation, select Yes and press
After the control operation is confirmed, the delay is activated.
Cancel the control by pressing any key when the delay is active.
Cancelling operation
Section 6
Operating procedures
.
to
97