Section 8
Commissioning
8.4.3.2
8.4.3.3
8.4.3.4
8.4.3.5
124
Adjusting the display contrast
Adjust the display contrast anywhere in the menu structure to obtain optimal
readability.
•
To increase the contrast, press simultaneously
•
To decrease the contrast, press simultaneously
The selected contrast value is stored in the non-volatile memory if you are logged in
and authorized to control the protection relay. After an auxiliary power failure, the
contrast is restored.
Changing display symbols
Use the keypad to switch between the display symbols IEC 61850, IEC 60617 and
IEC-ANSI.
1.
Select Main Menu/Configuration/HMI/FB naming convention and press
.
2.
Change the display symbols with
3.
Press
to confirm the selection.
The protection relay has to be rebooted if the WHMI display symbols
are changed. With the LHMI, the change takes effect immediately.
Changing the default view
The default view of the display is Measurements unless set otherwise.
1.
Select Main menu/Configuration/HMI/Default view and press
2.
Change the default view with
3.
Press
to confirm the selection.
Setting the system time and time synchronization
1.
Select Main menu/Configuration/Time/System time.
2.
Select the parameter with
3.
Press
, change the value with
4.
Repeat steps 2 and 3 to set the rest of the system time parameters.
and
and
or
.
or
.
or
.
or
and press
1MRS758754 B
.
.
.
again.
REC615 and RER615
Operation Manual