Using the local HMI help

1.
Press
to open the help view.
2.
Scroll the text with
3.
To close the help, press

Using the Web HMI

WHMI is disabled by default, and has to be activated in the protection relay
configuration. As secure communication is enabled by default, the WHMI must be
accessed from a Web browser using the HTTPS protocol.
1.
To enable the WHMI, select Main menu/Configuration/HMI/Web HMI
mode via the LHMI.
2.
Reboot the relay for the change to take effect.
3.
Log in with the proper user rights to use the WHMI.
To establish a remote WHMI connection to the protection relay,
contact the network administrator to check the company rules for IP
and remote connections.
Disable the Web browser proxy settings or make an exception to the
proxy rules to allow the protection relay's WHMI connection, for
example, by including the relay's IP address in Internet Options/
Connections/LAN Settings/Advanced/Exceptions.

Logging in

1.
Open Internet Explorer.
2.
Type the protection relay's IP address in the Address bar and press ENTER.
3.
Type the username with capital letters.
4.
Type the password.
button as a shortcut for clearing. The first three-second
or
if the help text exceeds the display area.
.