Appendix 4: Event Log Messages

LOG Event
Value
Description
Substitution attempt detected: a device communicates with the HUB
Sub. Attempt
ON
using the same RF address of another device correctly paired.
Field Ch A Jam
ON
Noise detected on RF Ch A.
Field Ch A
Back to normal condition.
Jam.
OFF
Field Ch B
ON
Noise detected on RF Ch B.
Jam.
Field Ch B
OFF
Back to normal condition.
Jam.
Link Fault
ON
Device is not communicating with the HUB
Link Fault
OFF
Back to normal condition
Tamper
ON
Device is not communicating with the HUB
Tamper
OFF
Back to normal condition
Interface flt
ON
Isolators active
Interface flt
OFF
Back to normal condition
Date time
ON
Date or time modified
edit
Batter A Low
ON
Battery A missing or low charge
Batter A Low
OFF
Back to normal condition
Batter B Low
ON
Battery B missing or low charge
Batter B Low
OFF
Back to normal condition
Alarm
ON
Device alarm
Alarm
OFF
Back to normal condition
Fault
ON
The fault is detailed with other log events
Fault
OFF
Back to normal condition
General Fault
ON
General device fault
General Fault
OFF
Back to normal conditions
Contamination
ON
Photo chamber contaminated
Contamination
OFF
Back to normal condition
In. Open
ON
Supervised module input open: EOL not found
In. Open
OFF
Back to normal condition
In. Short
ON
Supervised module input short: wiring short
In. Short
OFF
Back to normal condition
Out.Open
ON
Supervised module output channel open: EOL not found
Out.Open
OFF
Back to normal condition
Out. Short
ON
Supervised module output channel short: wiring short
Out. Short
OFF
Back to normal condition
Rel. Short
ON
Output activated
Rel. Short
OFF
Back to normal condition
Event Log
ON
Event log cleared
Cleared
PP5099/2023/Issue 1
Action
Look for the device/devices that caused the
substitution attempt: LEDs blink amber two
times and repeat the blinking periodically.
Remove batteries.
Power cycle the Loop Interface.
Optional: Re-pair device.
Check for external RF interference.
Check for external RF interference.
Check for the device condition and position
Check for the device condition and position
Loop connection lost/down
Loop connection restored
-
Change both device batteries
Change both device batteries
-
-
Check the device condition
Check Optical Detector device photo chamber
Check for device wiring and EOL
Check for device wiring and EOL
Check for device wiring and EOL
Check for device wiring and EOL
-
-
Page 27 of 27