Loop Address
This screen is used to change the address of the
device on the addressable loop.
This can be set to any value between 1 and 126.
Addresses assigned to other REACH devices paired
to the loop-interface will be skipped in this list, as
they are not available (unless changed first).
The Loop-Interface is not aware of other devices on
the addressable loop, so please refer to the fire panel
for a full list of available addresses.
Use the up/down arrows to change the loop
address.
Press 'Enter' to confirm.
Device-Specific Settings
This option will show in the [DEVICE MENU] as a
different entry for certain device types.
An Optical Detector shows
the detector's sensitivity mode.
Detector Sensitivity Modes that can be selected:
• High Sensitivity - suitable for clean
environments
• Medium Sensitivity - Standard sensitivity,
suitable for most standard applications
• Low Sensitivity - Low sensitivity, suitable
for contaminated environments or where
disturbances are expected such as shower
fumes.
OP. CH. SENS
which sets
[MODIFY DEVICE]
LOOP ADDRESS
OPT.CH.SENS
ABOUT
SELECT LOOP ADDRESS
002
[MODIFY DEVICE]
LOOP ADDRESS
OPT.CH.SENS
ABOUT
PP5099/2023/Issue 1
Page 15 of 27