With both batteries inserted into the product
correctly, move the pairing switch from the 'ON'
position to the '1' position.
Note: Ensure that the device had time to power-up after
battery insertion (LED should flash three times). If the
pairing switch is moved too soon, the device won't be
found. In this case, set the switch back to 'ON', remove
then re-insert the batteries and move the pairing
switch again.
Once the switch is moved, the RW1700-030APO Loop
Interface LCD should display 'DEVICE FOUND'.
Note: At this step, the RW1700-030APO Loop Interface
is writing critical settings to the device via the pairing
RF channel, then waiting for the device to reboot and
communicate back on the RF Channel Pair configured
during setup and with the correct System ID code.
Once the RW1700-030APO Loop Interface receives
a response from device being paired, it will read the
attributes of that device and confirm on the LCD what
type of product it is.
At this stage, the RW1700-030APO Loop Interface
will also automatically assign a loop address to that
product.
The [ADD DEVICE PROCESS] will pause at this
point to allow you to record the loop address of the
product.
To pair another product, select NEXT.
To finish pairing products, select EXIT.
Note: The first product will be auto-assigned as [Hub Address +1], then [Last Assigned Address +1] for each subsequent
product paired. These addresses can be changed manually before the system is released.
Note: Although the RW1700-030APO Loop Interface is wired-in to the loop and powered-on, it will not announce itself
or paired devices to the panel at the addresses set until setup is complete and the system is released. Each time the
Loop-Interface is in configuration mode, it and all associated wireless devices will stop responding to the panel until
configuration mode is exited again.
Note: REACH Heat Detector will ask which operating mode should be set, 'ROR' rate-of-rise or 'HT' static. Refer to the
product datasheet for details.
Note: REACH Open-Area AV products will ask whether a 'beacon' is present, as well as a sounder. This does not change
product operation but will prevent it from being correctly labelled in the Hub menu.
[ADD DEVICE PROCESS]
DEVICE FOUND
WAITING FOR RESPONSE
[PAIRING]
[ADD DEVICE PROCESS]
DEVICE TYPE:
OPT DET
PAIRED TO ADDRESS 254
EXIT
PP5099/2023/Issue 1
Page 13 of 27
NEXT