Figure 38 - Individual Series Do Connections; Figure 39 - Common Series Do Connections - Honeywell 900U02-0100 User And Installation Manual

Process & safety controller
Table of Contents

Advertisement

+24VDC
Sourcing
DO-32
900H32
Relay Output
900H01
9.5 V >= VALID HIGH <= 32.0 V
0.0 V >= VALID LOW <= 3.5 V
+24VDC
Relay Output
900H01
Sinking DO-16
900H02
9.5 V >= VALID HIGH <= 32.0 V
0.0 V >= VALID LOW <= 3.5 V
Sourcing
DO-32
900H32
Sinking DO-16
900H02
68
ControlEdge HC900 Process & Safety Controller User and Installation Manual
Relay Output
900H01
DI-16
900G02
Relay Output
OR DI-32
900H01
900G32
DI
DI-16
900G02
OR DI-32
900G32
Relay Output
900H01
DI
Relay Output
900H01
Note: DI Sense is inverted
Figure 38 – Individual Series DO connections
+24VDC
Relay Output
DI-16
900G02
or DI-32
900G32
DI
Relay Output
900H01
DI-16
DI
900G02
or DI-32
900G32
Note: DI Sense is inverted
Figure 39 – Common Series DO connections
+24VDC
DI-16
900G02
OR DI-32
900G32
DI
+24VDC
Relay Output
900H01
DI-16
900G02
or DI-32
900G32
Relay Output
900H01
DI
Note: DI Sense is inverted
900H01
DI-16
900G02
DI
or DI-32
900G32
75 VAC >= VALID HIGH <= 250 VAC
DI-16
900G02
or DI-32
900G32
DI
110/220
AC
Relay Output
900H01
DO-8
900H03
DI-16
DI
900G03
900G04
DI-16
DI
900G03
900G04
Note:
DI Sense is inverted when Load is placed
on High side (relay sinks power).
DI Sense is NOT inverted when Load is
located on Low side ( relay sources power).
110/220
AC
DO-8
900H03
DI-16
DI
900G03
900G04
0.0 V >= VALID LOW <= 20 VAC
Relay Output
900H01
DI-16
DI
900G03
900G04
Note:
DI Sense is inverted when Load is placed
on High side (relay sinks power).
DI Sense is NOT inverted when Load is
located on Low side ( relay sources power).
Revision 10
May 2019

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Controledge hc900900p01-0401900c75-0460

Table of Contents