Figure 60 - Ac Input Module Wiring Diagram - Honeywell 900U02-0100 User And Installation Manual

Process & safety controller
Table of Contents

Advertisement

AC Input Module Wiring
The AC Input Module has sixteen inputs. An example of AC Input Module wiring is shown in Figure 60.
Specifications for this module and for other modules are given in the Specifications section of this
manual.
Common Terminals
Two common terminals are provided for each group of eight inputs. Terminals 9 and 10 are connected in
the input module, and terminals 11 and 12 are connected in the module.
Jumper Comb
An optional two-position jumper comb is available as an option (for barrier style terminal blocks only) for
connecting digital common wiring at terminals 9 and 11 or terminals 10 and 12. See Figure 61.
Hazardous voltages exist at terminal blocks.
 Using switches at field devices, disconnect the field wiring from power sources before servicing.
Failure to comply with these instructions could result in death or serious injury.
110
ControlEdge HC900 Process & Safety Controller User and Installation Manual
Figure 60 – AC Input Module Wiring Diagram
Revision 10
May 2019