9.5.

Failover

Automatic Failover
Triggered on any of the following conditions of the Lead Controller:
Loss of communications with I/O Rack(s)
Processor exception conditions
Error conditions that occur in the following areas will not cause a failover:
Loss of communications to a Host on a network
Loss of communications to Modbus Slave devices
Loss of communications to Operator Interface
Loss of communications with a Peer controller
During the transition from the Lead to the Reserve, analog and digital output status is
maintained at the I/O racks.
Manual Failover
Via Key Switch on the Redundancy Switch Module in the Redundant Controller Rack. For
manual failover with keyed switch, turn key to Failover and hold it there until both Reserve
lights are on, then release the key.
Via Software Command from HC Designer & HC Utilities PC Software
Via Software Command from Modbus / TCP & Serial Modbus RTU Hosts
Via Software Command from 900 Control Station.
Via input to RSTAT Function Block to initiate failover (User can configure logical conditions
such as loss of communication handshake between Host and Controller to initiate failover).
Failover Performance
Failure condition detection and failover from Lead to Reserve CPU executed in 4 analog control cycles or
less.
Redundancy Diagnostic Monitoring
From HC Designer and HC Utilities PC Software
Redundant System Status - current status of Lead/Reserve Controller CPU's
On-Line Monitoring, Controller Diagnostics, Communications Loop-Back tests
Redundant Link Status – status of communications between Lead and Reserve controllers.
Lead CPU status
Reserve CPU status
Scanner status
9.6.

File Download/Upload Functions

See page 171.
Revision 10
ControlEdge HC900 Process & Safety Controller User and Installation Manual
May 2019
183