Once the appliance is installed turn the power supply on, then turn the on / off
switch to the 'I' position and note the unit starts. Then carry out the following: -
• Check that the compressor is running
• Leave the appliance to run for approximately 15 minutes
• Observe the coils through the filter grille to confirm frost formation or
weeping of the evaporator coil
o If the air temperature is below 25°C, an even coating of frost
should cover the entire evaporator coil.
o If the air temperature is above 25°C, frost and/or droplets of
condensed water should cover the entire evaporator coil.
• When the unit is operated in an ambient of less than 15°C, a defrost
cycle should occur. This will be at intervals of no more than every hour
and will last no more than 5 minutes. The exact time is impossible to
predict as the unit is fitted with a temperature sensitive defrost control.
After using the appliance, turn it off for 5 minutes to allow the condensate on
the coils to drain into the pump reservoir. Then turn the appliance back on and
press the momentary purge switch for 20 to 30 seconds to evacuate the water
from the pump reservoir.

OPERATION

Page 6 of 12
Drawing : - TPC596
Issue
: - 2
Date
: - 08/06/23