Operation - EIP CD85 Owner's Manual

Industrial dehumidifier
Table of Contents

Advertisement

The following procedures should be followed to test the CD85 for correct

operation:

1.
After unpacking, examine all external features to confirm damage-
free shipment. Report all defects and damage at once. Connect the
power cable to a grounded 15 Amp electrical outlet.
2.
Check dehumidification process as follows:
TO ENSURE CONTINUED FULL EFFICIENCY OF THE
DEHUMIDIFEIR, MAINTENANCE PROCEDURES SHOULD BE
A.
Place unit on a level surface.
B.
Start up unit by turning the humidistat control knob until the
unit turns on.
C.
Check that the compressor is running.
D.
Leave the machine running for 15 minutes.
E. Observe the evaporator coils through the evaporator filter panel
i. If the air temperature is below 80° F, an even coating of
ii. If the air temperature is above 80° F, frost and/or droplets
F. After continuous running time of approximately 55 minutes, the
unit will enter "Hot Gas" defrost mode for 5 minutes and then
automatically return to normal operation.
If, after carrying out the above procedures, the unit does not appear to
function properly, refer to the Trouble Shooting section, which follows,
or contact the Factory Service Center.
ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT
LEAST FIVE MINUTES BEFORE RESTARTING.
OPERATION
PERFORMED AS FOLLOWS:
frost should cover the entire evaporator coil
of
condensed
water
evaporator coil.
CAUTION:
Page 7 of 15
Drawing : - TPC361
Issue
: - 1
Date
: - 21/06/11
should
cover
the
entire