Package contents for concealed installation (Fig� 3�1)
Package contents for surface-mounted installation (Fig� 3�2)
Product components (Fig� 3�3)
A Load module, power supply lead, surface-mounted
B Load module, power supply lead, concealed installation
C Designer trim, round or square
D Sensor module
Product dimensions
Ceiling / wall mounting, surface-mounted and concealed wiring (Fig� 3�4)
4� Electrical installation
An optional corner wall mount is available for mounting the HF 3360 COM1.
(Prod. No. 035174 white)
The supply lead consist of three wires:
L
= phase conductor (usually black, brown or grey)
N = neutral conductor (usually blue)
PE = protective-earth conductor (green/yellow)
= switched phase conductor (usually black, brown or grey)
Note on manual override function (Fig� 4�1):
A power switch for switching ON and OFF can be installed in the mains supply lead.
This is a prerequisite for the manual override function. (➔ "6� Function")
If the rubber seal is damaged, the cable entry openings must be sealed with an M16
or M20 (at least IP54) double seal cable gland.
For mounting on the wall, a condensation water drainage hole (Ø 5 mm drill bit) is
marked next to the rubber seal. This must be opened if necessary.
Connection examples (Fig� 4�2)
a Light without neutral conductor
b Light with neutral conductor
c Connection by means of two-circuit single-interruption switch for manual
and automatic operation
d Connection via two-way switch for manual override and automatic
operation
Setting I: Automatic operation
Setting II: Manual operation, light permanently ON
22
Note: The system cannot be switched OFF, it is only possible to select operation via
setting I or II.
a) Load, lighting max. 2000 W (refer to Technical specifications)
b) Sensor connection terminals
c) Indoor switch
d) Indoor two-circuit single-interruption switch, manual, automatic
e) Indoor two-way switch, automatic, light permanently ON
Connecting several sensors in parallel (not illustrated)
In this case, it is important not to exceed a sensor's maximum connected rating. In
addition, all units must be connected to the same phase. As many as 10 sensors can
be connected in parallel.
Note: The cable between two sensors must be no more than 50 m in length.
5� Mounting
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location, taking the reach and
motion detection into consideration.
Installation procedure
Wall-mounting, concealed power supply lead (Fig� 5�1)
Ceiling mounting, concealed power supply lead (Fig� 5�2)
Wall-mounting, surface-mounted power supply lead (Fig� 5�3)
Ceiling mounting, surface-mounted power supply lead (Fig� 5�4)
• Switch OFF power supply.
• Detach designer trim from sensor module.
• Disconnect sensor module from the load module.
• Connect to mains power supply.
- Surface-mounted power supply lead. (Fig� 5�5)
- Concealed power supply lead. (Fig� 5�6)
• Insert fastening screw and mount load module.
• Fit sensor and load module together and screw into place.
• Switch ON power supply.
• Set functions. (➔ "6� Function")
• Fit decorative trim panel.