Startup Mode; General Safety Functions - Ecoflam BLU TS 3000.1 PRE HT Manual

Table of Contents

Advertisement

EN
GAS OPERATING MODE - GENERAL SAFETY FUNCTIONS
START-UP MODE
As soon as the furnace system is required
to supply heat, the burner control circuit
will close and the program flow started.
When the program has come to its end,
the burner will be turned on.
An automatic test is made for the tightness
of the gas valves prior to each burner start.
The air damper is in its closed position
when the burner is out of operation.
The electric actuator will open the closed
air damper to its full-load position so that
the burner will ventilate the furnace and
the exhaust hoods with the specified air
rate.
Shortly after the preventilation process has
been started the lack-of-air cut-out must
change over to operating position within a
certain time, i.e. the minimum air pressure
setting must be reached and maintained
until the burner is turned off. At the end of
the specified pre-ventilation time the air
damper will be moved into its partial-load
position in a linked control concept with the
gas damper.
The ignition transformer will be started.
At the end of the pre-ignition time the gas
valves will be opened to allow gas to flow
into the burner.
The ignition electrodes incorporated in the
burner will ignite the ignition gas.
The UV cell gives flame signal to

GENERAL SAFETY FUNCTIONS

In case a flame does not develop when
starting the burner (fuel release) the
burner will shut off at the end of the safety
period (safety lock-out).
A safety lock-out will also occur in the case
of flame failure during operation, air flow
failure during the pre-ventilation phase and
pressure failure during the whole period of
burner operation.
Any failure of the flame signal at the end of
the safety period and a flame signal during
10
www.ecoflam-burners.com
control box so that the safety shut-off
valves will be opened.
The gas will be fed to the gas nozzles via
the gas damper while combustion air is
supplied by the fan.
Gas and air will be intensively mixed in the
mixing unit and ignited by the spark.
After the safety period has run down the
ignition spark will be turned off.
Attention:
If there are shut-off dampers in the flue
gas tract they must be completely open.
Otherwise there will be a high danger of
low-speed detonation or explosion!
GAS OPERATING MODE
After the flame has developed the load
regulator will be enabled which brings the
burner into its operating position.
The load regulator will now control the
burner automatically between its partial-
load and full-load stages. Depending on
the heat demand, the electric actuator of
the compound control system will be fed
with the OPEN or CLOSE command via
the regulator and thus increase or
decrease the gas and air flow rates.
This compound control system will vary
the positions of the gas control valve and
the pre-ventilation phase (external light
control) will result in a safety lock-out with
the automatic furnace controller being
locked.
The trouble is indicated by the trouble
signal lamp lighting up.
The automatic furnace controller can be
unlocked immediately after a safety lock-
out by pressing the unlocking key. The
program unit will return to its starting
position and proceed with the restart of the
burner.
air damper and thus regulate the gas flow
rate in a linked concept with the air flow
rate. The burner can either be controlled
by a 2-stage sliding or, if a respective
controller is provided, a stepless control
concept.
The stepless control will allow the burner
to be operated at any desired stage
between its partial-load and full-load
positions.
The burner will always be turned off out of
its partial-load position.
The air damper will be closed when the
burner is out of operation and will thus
prevent cold air flowing through the burner
chamber, heat exchanger and chimney.
The interior cooling losses will thus be
greatly minimized.
A voltage failure will result in a regular
shut-off of the burner. Upon voltage
recovery there may be an automatic
restart unless another interlock is
provided, e.g. by the safety system. In any
case of trouble the fuel oil supply will be
shut off right away. The program unit will
stop at the same time causing also the
trouble location indicator to stop.
The symbols will indicate the kind of
trouble.
420010717300

Advertisement

Table of Contents
loading

This manual is also suitable for:

Blu ts 4000.1 pre ht

Table of Contents