Command/Response Reference
Total Number of Packets
Received (Response)
Total Number of Receive
Errors (Response)
Total Number of Packets
Sent (Response)
Total Number of Errors
Sent (Response)
Total Number of Send
Collisions (Response)
Precautions
Response Codes
7-3-4

INTERNODE ECHO TEST

Command Block
Response Block
Address Disagreement
The address conversion method was set for automatic generation, but the
node address and the last byte of the local IP address do not agree, or other
host sections are 0.
EEPROM Error
An error occurred in the EEPROM memory in the Ethernet Unit.
The total number of packets received by the Ethernet Unit is returned.
The total number of errors detected while the Ethernet Unit was receiving is
returned. The types of error detected are short packet errors, alignment
errors, CRC errors, frame length errors (received frame: 1,515 bytes or more),
and communications controller overflow errors.
The total number of packets sent by the Ethernet Unit is returned.
The total number of packet errors detected while the Ethernet Unit was send-
ing is returned.
The number of packets damaged by 16 collisions with data from other nodes
during Ethernet Unit transmissions.
Counting of the total number of packets received, total number of receive
errors, total number of packets sent, total number of errors sent, and total
number of send collisions is discontinued when the counted value reaches the
maximum value.
Response code
0000
Normal
1001
Command too large
Runs the echo test between specified nodes.
08 01
1,998 bytes max.
Command
Test data
code
08 01
Command
Response
code
code
Description
1,998 bytes max.
Test data
Section 7-3