Omron CS Series Operation Manual page 174

Ethernet units construction of networks
Hide thumbs Also See for CS Series:
Table of Contents

Advertisement

Communicating between OMRON PLCs
(Continued from previous page.)
Execution
condition (See note.)
0000.01 A202.07 1200.00
1200.03
1200.02
1200.02 A202.07
(See note.)
1200.02 A219.07
1200.02 1200.03 A219.07
Note
148
S
KEEP
120002
@MOV(21)
D00005
@MOV(21)
D00006
@MOV(21)
D00007
@MOV(21)
D00008
@MOV(21)
D00009
@RECV(98)
D00005
DIFU(13)
120003
121001
@XFER(70)
D00040
1. With CS/CJ-series PLCs, the Communications Port Enabled Flags at bits
0 to 7 in word A202 turn OFF even when the PCMR(260) instruction is be-
ing executed using the ports corresponding to those flags.
2. Before using the sample program as is, confirm that the memory areas
(words and bits) used in the sample program are not already being used in
the user program o r by Special I/O Units.
When the Communications Port Enabled Flag for port 7
is ON, and SEND(090) is not being executed, the trans-
mission execution program will start when execution
condition CIO 0000.01 turns ON.
R
Input CIO 1200.02 remains ON from the start of
RECV(098) execution until completion.
#0010
Control Data Creation
Word
Contents
D00005
00
10
#0003
D00006
00
03
D00007
20
00
#2000
D00008
07
05
#0705
D00009
00
00
#0000
A total of 16 words of data beginning from word A100
at network number 3, node number 32, unit address 0
(the PLC) is received at word CIO 2000 onwards of the
local node.
A100
2000
Reset Input Creation
Reception Error Display
Reception Data Processing
If there is no reception processing completion error, the
#0016
16 words of data received from word CIO 2000 on-
2000
wards is stored at D00040 onwards.
Section 6-6
Meaning
Number of reception words = 16
Source network number = 3
Source node number = 32
Source unit address = 0
Response required.
Communications port No. used = 7
Number of retries = 5
Response monitor time = Default