Omron CS Series Operation Manual page 89

Ethernet units construction of networks
Hide thumbs Also See for CS Series:
Table of Contents

Advertisement

Setup
Item
Conversion
Destination IP Address
(Change Dynamically)
Baud Rate
TCP/IP keep-alive
IP Address Table
IP Router Table
FTP
Login
Password
Port No.
High-speed Socket Ser-
vices
Note
Select any of the following as the method for finding and converting IP
addresses from FINS node addresses. (Enabled for FINS/UDP only.)
• Automatic generation (dynamic): Auto (dynamic)
• Automatic generation (static): Auto (Static)
• IP address table method: Table used
• Combined method: Mixed
Select to dynamically change the remote (destination) IP address for
FINS/UDP. To prohibit dynamic changes, deselect this box.
Select the Ethernet baud rate for the Ethernet Unit.
Select either automatic detection or 10Base-T. (For 100Base-TX, select
automatic detection.)
Set the liveness-checking interval. When socket services using either
FINS/TCP or TCP/IP are used, the connection will be terminated if there
is no response from the remote node (either a server or client) within the
time set here. (Enabled for socket services using FINS/TCP or TCP/IP
only.)
Setting range: 0 to 65,535 minutes
This setting applies to the keep-alive setting for each connection set
with the FINS/TCP tab.
Set the IP address table that defines the relationship between FINS
node addresses and IP addresses.
With FINS/UDP, this is enabled only when the IP address table method
is set as the IP address conversion method.
Set when the Ethernet Unit is to communicate through the IP router with
nodes on another IP network segment.
Sets the login name for connecting to the Ethernet Unit by FTP.
Sets the password for connecting to the Ethernet Unit by FTP.
Set the FTP port number for the Ethernet Unit.
There is normally no need to change this number.
Two ports are used for FTP: a control port and a data transfer port. This
setting sets only the control port, and then the data transfer port uses
the number that is one less than the control port.
Selecting this option improves the performance of processing for send-
ing and receiving using specific bits for socket services. For information
on communications performance, refer to 6-9-5 Times Required for
Sending and Receiving for Socket Services in the Ethernet Units Con-
struction of Applications Operation Manual. When the High Speed
Option is selected, socket services that are implemented using a
CMND(490) instruction will cause an error.
(1) The setting to enable or disable dynamic changing of remote IP address-
es is available for Ethernet Units with Unit Ver. 1.3 or later.
(2) Make settings using the unit settings function in the CX-Programmer (to
be included in version 5.0 and higher) or using the Web function (refer to
Appendix G Ethernet Unit Web Function).
(3) The Enable CIDR Option and High Speed Option for performance of
socket service are supported starting with unit version 1.5.
Contents
Section 3-1
Default
Auto (dynamic)
Checked
(Change Dynami-
cally)
Auto
0
(120 minutes)
None
None
None
None
("CONFIDENTIAL")
0
(Number 21 is
used.)
Disabled
63