Section 7: Modbus I/O List

October 2022
Section 7: Modbus I/O List
The following paragraph describes the I/O composition of the Modbus interface implemented in the
XTE3000 Modbus RTU module. The XTE3000 Modbus RTU module concentrates all the available data
in the Holding Register Data Area, but to grant the backward compatibility with the ICON2000v4,
it maintains also the former data structure.
The Modus interface is divided in four areas and each area is accessible via the specific Modbus
Function Code as described in Section 8.
7.1

Discrete Inputs

In the Discrete Input Data Area, the XTE3000 Modbus RTU module implements the same 32 discrete
inputs available on ICON2000v4.
Status of discrete inputs is indicated as 1 = ON and 0 = OFF.
The following table shows the discrete inputs implemented in the XTE3000 Modbus RTU module:
Table 1.
Input Status Number
ICON2000v4 legacy data block
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
10
Installation, Operation and Maintenance Manual
Input Status Address
Description
0
Close Limit
1
Open Limit
2
Actuator Moving
3
Monitor Relay
4
Selector in LOCAL
5
Selector in REMOTE
6
Alarm
7
Warning
8
DIN1 (See Note 1)
9
DIN2 (See Note 1)
10
DIN3 (See Note 1)
11
DIN4 (See Note 1)
12
DIN5 (See Note 1)
13
DIN6 (See Note 1)
14
Interlock Open
15
Interlock Close
16
Fail Safe Action
17
Actuator Opening
18
Actuator Closing
19
Selector in OFF
20
ESD/PST Control (see Section 11.1 for details)
21
Hardwired Remote Mode
22
Positioner Mode
23
Motor Operation Inhibited
24
Channel 1 Active
25
Hardwired Open Command
26
Hardwired Close Command
27
Hardwired Stop Command
28
Hardwired BUS-on
29
Base Card Communication Error (Reserved)
30
Reserved (always 0)
31
Reserved (always 0)
VCIOM-15081-EN Rev. 7