11. Last Close Torque Curve, Reference Close Torque Curve, Last Open Torque Curve,
Reference Open Torque Curve:
These registers contain several types of data; the combination of this data is described, byte per byte,
in the table below:
Values
1
- 101
st
102
nd
103
rd
104
th
105
th
106
th
107
th
108
th
109
th
110
th
111
th
113
th
115
th
Each register contains 2 bytes of torque curve data.
*The index of these bytes indicates the actuator position.
Example: index 1 indicates the output torque on the position 0%; index 2 indicates the output torque
on the position 1%, and so on).
Modbus I/O List
Description
Torque Samples* (One sample for each byte)
st
Date of torque curve (BCD format): Day
Date of torque curve (BCD format): Month
Date of torque curve (BCD format): Year minus 2000
Time of torque curve (BCD format): seconds
Time of torque curve (BCD format): minutes
Time of torque curve (BCD format): hours
Electronic temperature (signed char, engineering unit: °C)
Terminal board temperature (signed char, engineering unit: °C)
Mot/speed temperature (signed char, engineering unit: °C)
- 112
Voltage. First byte contains most significant bits. (engineering unit: V)
th
- 114
Closing/Opening time. First byte contains most significant bits (engineering unit: seconds)
th
- 128
Reserved data