Installation, Operation and Maintenance Manual
VCIOM-15081-EN Rev. 7
19. Aux. Analog Input 12 bit:
This register contains the Auxiliary Analog Input value scaled on 0-4095 (12 bit).
If the Auxiliary Analog Input is lower or equal to 4 mA, it assumes the value 0.
If the Auxiliary Analog Input is higher or equal to 20 mA, it assumes the value 4095.
20. Clear Alarms and Warnings Log
This register is available from Modbus Interface firmware revision 2.02. It's always read as 0.
Values
0
1
If it's set to 1, it's automatically cleared by the device.
21. Reset Alarms and Warnings
This register is available from Modbus Interface firmware revision 2.02. It's always read as 0.
Values
0
1
If it's set to 1, it's automatically cleared by the device.
22. Actuator Type
These registers are available from Modbus Interface firmware revision 2.03.
Modbus I/O List
Description
No command
Clear Alarms and Warnings Log command
Description
No command
Reset Alarms and Warnings command
Section 7: Modbus I/O List
October 2022
33