9.3

Fail Safe Function

This function is available only if requested on order. It allows configuring the action of the actuator in
case of loss of the BUS signal. The action takes place only if the local selector is in REMOTE and if BUS
is operating. When the BUS signal restores, also the actuator restores at its normal functioning.
The fail safe function can be configured via either BUS or local operator interface.
The hardwired controls ESD and INTERLOCKS override the Fail Safe action according to the following
diagram (the hardwired controls INTERLOCKS are available only if optional modules APTM/APTM1 or
PSM/PSM1 are present.
OP/CL Controls
Lowest Priority
The following options can be configured:
Configuration Procedure
View Procedure
Configuration of XTE3000
Fail Safe Action
Fail safe action: open, close, stay-put, go to position %, no action (OFF)
Length of the delay time before than the fail safe action takes place
(length = 10 seonds + configured value)
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions "entering the setup
mode." When the message of display is "SETUP MODE OK?" press YES. Press YES to select
actuator setup menu, press NO to scroll the list of available routines and then press YES to
select FAIL SAFE.
Press YES if the configured ACTION is correct (open, close, stay-put, go to position xx%, off),
or press NO to change, then press YES.
Press YES if the configured value of the DELAY is correct (from 0 to 255 seconds), or press
NO to change, then press YES.
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions "entering the view
mode." When the message of display is "VIEW MODE OK?" press YES. Press YES to select
actuator setup menu, press NO to scroll the list of available routines and then press YES to
select the routine (FAIL SAFE).
Press YES to scroll the list of parameters.
Section 9: Configuration of XTE3000
Interlocks
ESD
October 2022
Highest Priority
49