Akai AK-T25R32 Installation Manual page 18

2.5kw reverse cycle inverter split system air conditione

Advertisement

Installation (Cont.)
Connecting the pipes
Screw the flare nuts to the outdoor unit coupling with the same tightening
procedures described for the indoor unit. To avoid leakage, pay attention to
the following points:
• Tighten the flare nuts using two
wrenches, taking care not to
damage the pipes (Fig. 17).
• If the tightening torque is not
sufficient, there will probably be
some leakage. With excessive
tightening torque there may also
be some leakage, as the flange
could be damaged.
• The best way to tighten the
connections is using a fixed
wrench and a torque wrench, as
illustrated in Fig. 12 on page 15.
Bleeding
Air and humidity left inside the
refrigerant circuit can cause
compressor malfunction. After
having connected the indoor
and outdoor units, bleed the air
and humidity from the refrigerant
circuit by using a vacuum pump
(Fig. 18). Detailed instructions
follow on the next page.
18
1300 886 649 (AUS) 0800 836 761 (NZ) |
Connection pipes
Liquid tap
Service port nut
Fig. 18
Service port
After Sales Support
Flare nuts
Gas tap
Indoor unit
Liquid valve
Gas valve
Protection caps
Vacuum pump
info@tempo.org
Fig. 17