Connecting; Safety When Connecting Up - Siemens SIMATIC NET SCALANCE XR-500 Operating Instructions Manual

Table of Contents

Advertisement

Connecting

6.1

Safety when connecting up

Safety notices
When connecting up the device, keep to the safety notices listed below.
Safety information for devices with 24 V DC power supply
Observe the following note for device variants with supply voltage 24 V DC:
Operation only with safety extra-low voltage
The device is designed for operation with a directly connectable safety extra-low voltage
(SELV). (This does not apply to 100 to 240 V devices).
This means that only safety extra-low voltages (SELV) complying with IEC 60950-1 / EN
60950-1 / VDE 0805-1 may be connected.
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
Suitable fusing for the power supply cables
The current on the terminal must not exceed 25 A.
Use a fuse, that protects against currents > 25 A. The fuse must meet the following
requirements:
In areas according to NEC or CEC:
• Suitable for DC (min. 60 V / 25 A)
• Breaking current at least 10 kA
• Approval according to ANSI/UL 248-1
• Suitable for the protection of DC power supply circuits
In other areas:
• Suitable for DC (min. 60 V / 25 A)
• Breaking current at least 10 kA
• Approval in compliance with IEC 60127-1 / EN 601127-1
• Breaking characteristics: B or C for circuit breakers and fuses
• Suitable for the protection of DC power supply circuits
SCALANCE XR-500
Operating Instructions, 09/2018, A5E03275845-12
WARNING
6
59