Daikin Clima-Flex IOM CLIM Series Installation, Operation And Maintenance Manual page 53

Air-cooled fixed compressor chiller water generator unit
Table of Contents

Advertisement

Vdf Compressor Controller
• The frequency converter is now programmed according to the
default settings.
This procedure initializes everything except:
• 15-00 Operating hours
• 15-03 Power On
• 15-04 Over Temperature
• 15-05 Over voltage
DATA TRANSFER FROM THE LCP TO THE
FREQUENCY CONVERTER
NOTES: Stop the motor compressor before performing this
operation.
1. Go to 0-50 LCP Copy.
2. Press [OK].
3. Select [2] All from LCP.
4. Press [OK] again.
5. The parameter settings stored in the LCP are transferred to
the frequency converter indicated by the progress bar. When
100% is reached, press [OK].
PARAMETER SELECTION
In the main menu mode, the parameters are divided into groups.
Use the navigation keys to select a parameter group.
Se puede acceder a los siguientes grupos de parámetros:
• - 0-** Operation/Display
• - 1-** Load/Motor
• - 3-** Reference/Ramps
• - 4-** Limits/Warnings
• - 5-** Digital input/output
• - 6-** Analog input/output
• - 7-** Controls
• - 8-** Communication and options
• - 13-** Intelligent logic
• - 14-** Special functions
• - 15-** Drive information
• - 16-** Data readouts
• - 25-** Cascade controller
• - 28-** Compressor functions
After selecting a parameter group, select a parameter with the
navigation keys. The middle section of the display shows the
number and name of the parameter as well as the value of the
selected parameter.
Figure 41. Screen example - Parameter selection
www.clima-flex.com
DATA CHANGE
The procedure for changing the data is the same in both the Quick
Menu and the Main Menu mode.
Quick menu and in the main menu mode.
Press [OK] to change the selected parameter. The procedure for
changing the data depends on whether the selected parameter
represents a numerical data value or a text value.
MODIFICATION OF A TEXT VALUE
If the selected parameter is a text value, change the value by
pressing the [▲]/[▼] navigation keys. The [▲] key increases the
value and [▼] decreases the value. Place the cursor on the value
and press the [OK] key to save.
CHANGE A GROUP OF NUMERICAL
VALUES
If the selected parameter represents a numerical data value,
change it by pressing the navigation keys. Press [<]/[>] to move
the cursor horizontally. Press the [▲]/[▼] key to change the data
value. The [▲] key increases the data value and the [▼] key
decreases the data value. Place the cursor on the value and
press [OK] to save.
Figure 42. Screen example
53
iom-clim-cf-eng