Unit Controller Operation
INPUTS AND OUTPUTS
The configuration of the inputs and outputs depends on the initial configuration of the system.
The tables in this section show the inputs and outputs assigned to each type of configuration as well as the port used for the "Mother"
unit (whose capacity is regulated by an inverter or an unloader) and the "Child" units.
Key: CO is for Cooling only and HP is for Heat Pump.
Figure 24. Analog inputs of the pCo (Mother Unit)
PORT
CO AIR
U1
INJECTION
U2
RETURN
U3
FREEZING
U4
MAIN RETURN
U5
MAIN INJECTION
U6
TEM. COND
U7
-
Figure 25. Digital inputs of the pCo (Mother Unit)
PORT
CO AIR
U9
-
ID1
HIGH PRESSURE
ID2
LOW PRESSURE
ID3
REMOTE START
ID4
MOTOR SAVER
Figure 26. Analog inputs of pCo 0.5-3.5 Vdc (Mother Unit)
PORT
CO AIR
U8
EVAPORATOR FLOW
U8
-
NO7
SECOND STAGE
NO8
-
Figure 27. Digital outputs of the pCo (Mother Unit)
PORT
CO AIR
NO1
COMPRESSOR
NO6
PUMP
NO7
FAN
NO8
-
Figure 28. Analog outputs of the pCo (Mother Unit)
PORT
CO AIR
Y1
INVERTER/SSR
Y2
INVERTER FAN
www.clima-flex.com
HP AIR
CO WATER
INJECTION
INYECCIÓN
RETURN
FREEZING
CONGELACIÓN
MAIN RETURN
RETORNO PRINCIPAL
MAIN INJECTION
INYECCIÓN PRINCIPAL
TEM. COND
INYECCIÓN DEL COND.
-
HP AIR
SELECTOR
HIGH PRESSURE
LOW PRESSURE
REMOTE START
MOTOR SAVER
HP AIR
EVAPORATOR FLOW.
-
SECOND STAGE
REVERSIBLE VALVE
HP AIR
COMPRESSOR
PUMP
FAN
REVERSIBLE VALVE
HP AIR
INVERTER/SSR
INVERTER FAN
RETORNO
MAIN RETURN
MAIN INJECTION
COND. INJECTION
-
COND. RETURN
CO WATER
-
HIGH PRESSURE
LOW PRESSURE
REMOTE START
MOTOR SAVER
CO WATER
EVAPORATOR FLOW
COND. FLOW
-
-
CO WATER
COMPRESSOR
PUMP
-
-
CO WATER
INVERTER/SSR
INVERTER FAN
35
HP WATER
TIPO
INJECTION
NTC
RETURN
NTC
FREEZING
NTC
NTC
NTC
NTC
NTC
HP WATER
SELECTOR
HIGH PRESSURE
LOW PRESSURE
REMOTE START
MOTOR SAVER
HP WATER
EVAPORATOR FLOW
COND. FLOW
-
-
HP WATER
COMPRESSOR
PUMP
-
REVERSIBLE VALVE
HP WATER
INVERTER/SSR
INVERTER FAN
iom-clim-cf-eng
TYPE
0-10 V
0-10 V