20.1. LABELING, CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS

IV
Extract room(s) air fan.
PV
Supply air fan.
Water
heater
circulatory
M4
pump.
M2
Supply/Extract air damper ac-
M3
tuator.
M5
Water cooler valve actuator.
M1
By-pass actuator.
DX cooler or water heater cir-
DX
culatory pump control.
M6
Water heater valve actuator.
Water heater antifreeze ther-
mostat.
T1
+
+
Water heater antifreeze re-
TV
turn heat carrier temperature
sensor.
Fresh (ambient) air tempera-
TL
ture sensor.
20
| EN
Contact
No.
Labeling
X10
X8
X31
X29
X12
X14
X15
X23
X35
1
PUMP
X35
2
AC.N
X35
3
AC.N
X35
4
EXT+
X35
5
EXT-
X3
RS485_2
X4
RS485_1
X32
1
LOW
X32
2
MID
X32
3
HIGH
X32
4
COM
X33
1
TIMER
X33
2
COM
X33
3
VAL+
X33
4
VAL-
X33
5
VAL
X33
6
DMP+
X33
7
DMP-
X33
8
DMP
X33
9
CHIL
X33
10
COM
X33
11
ALARM
X33
12
ANTI.F
X33
13
B.0.10
X33
14
COM
X33
15
A.0.10
X33
16
COM
X33
17
+24V
X33
18
COM
X33
19
T.WAT
X33
20
COM
X33
21
T.OUT
X33
22
COM
X33
23
T.SET
X33
24
COM
Description
L(230V/50Hz power supply)
N(230V/50Hz power supply)
Electric heater
Electric preheater/rotor ON/OFF
230V/50Hz
Voltage of Normal speed for air
fans
Voltage of Min speed for air fans
Power to exaust air fan IV
Power to supply air fan PV
Pump motor ON/OFF 230V/50Hz
N pump motor
N damper motor
L
damper
motor
ON/OFF
230V/50Hz (delay of 3 minutes af-
ter stopping fans and heaters)
L
damper
motor
ON/OFF
230V/50Hz
ModBus
Remote controller (FLEX)
Electrical heater guard from over-
heating
Rotor guard
BOOST, increase the flow of air.
COM
Stop
COM
Cooling
valve
opening
PWM
24v/50hz
Cooling
valve
closing
PWM
24v/50hz
Cooling
valve
common
Pulse
24v/50hz
Bypass damper opening PWM
24v/50hz
By-Pass damper closing PWM
24v/50hz
By-Pass damper common PWM
24v/50hz
DX cooling ON/OFF 24V
COM
Indicates when fans fail ON/OFF
24V
Indicates when fans running ON/
OFF 24V
Electric/Water heater controll sig-
nal 0-10V
COM
Bypass/Rotor 0-10V
COM
24VDC
COM
Return water temperature sensor
COM
Outdoor sensor
COM
Extract air fan 0-10V pressure,
CO2 transmitters
COM
I/O
Max. load
Min. load
type
[ A ]
[ mA ]
I
-
-
I
-
-
O
16A
100
O
16A
100
I
-
-
I
-
-
O
4.2A
100
O
4.2A
100
O
3A
100
O
3A
100
O
3A
100
O
3A
100
O
3A
100
I/O
-
-
I/O
-
-
I
-
-
I
-
-
I
-
-
-
-
-
DI
-
-
-
AO
-
-
AO
-
-
AO
-
-
AO
100mA
-
AO
100mA
AO
100mA
DO
0.05mA
-
-
DO
0.05mA
-
DO
0.05mA
-
AO
5mA
-
-
-
-
-
-
-
O
0.1A
-
-
-
-
AI
-
-
-
-
-
AI
-
-
-
-
-
AI
-
-
-
-
-
RIRS 1200-5500 V EKO 3.0 v2019.06