Section 2: Framing

1). Frame in the enclosure for the unit with framing materials. The
framed opening for the assembled fireplace shown below in table
as the MINIMUM dimensions.
A
B
DRSQ42
72''
51''
A
B
DRSQ46
84''
55''

Recommended flooring considerations

Flooring such as Luxury Vinyl Plank (LVP) and other vinyl flooring can
be sensitive to radiant heat and changes in temperature. If using vinyl
flooring we recommend you install the fireplace in one of the ways
shown below.
Floor mounted fireplace
24" Min.
hearth
Hearth
The minimum width of the
hearth is equal to the width of
the fireplace.
XG0232 - 043021
C
D
E
F
21''
45''
627/16''
441/8''
C
D
E
F
22''
49''
673/8''
475/8''
Raised fireplace
16" Min.
rise
Flush
Vinyl
Flooring
Raise the fireplace 16" above the
floor to allow for vinyl flooring
to be installed flush to the wall.
(Measured from floor to the
bottom of the door opening)
NOTE: When constructing the framed opening, please ensure there is
access to install the gas line when the unit is installed

Wall framing Dimensions

G
1
G
1
3"
B

Corner framing

F
Figure 3.b Framing dimensions (Straight wall & Corner Installation).
To avoid the possibility of insulation or vapour barrier coming in
contact with the fireplace body, we recommended that the inner
chase be finished (i.e. drywall / sheetrock). Follow local codes for
Installation
DRSQ
42 46
HEADER MUST BE ON EDGE
D
C
G
E
WARNING
requirements in your area.
DRSQ
A
9