Description Of The Screens - Salicru EQUINOX EQX2 4002-HT User Manual

Three-phase hybrid solar inverters connected to the grid
Table of Contents

Advertisement

Available languages

Available languages

7.1. DESCRIPTION OF THE SCREENS.

When the inverter is started, the  following interfaces will be
displayed on the OLED screen, which allows the user to check
different types of operating information, as well as to change the
inverter settings. Please refer to the following screen operation
flow chart for more details:
"V-Ipv1/2" screen menu.
1.
Screen 1.1
Screen X.X Indicator of the voltage and current of
the solar field connected to MPPT 1 and 2.
Batt. param.
2.
Screen
2.1. Battery voltage, current and power indicator.
"V grid" screen menu.
3.
Screen 3.1
Indicator of the grid voltage.
"I grid" screen menu.
4.
Screen 4.1
Indicator of the current supplied to the installation.
"F grid" screen menu.
5.
Screen 5.1
Indicator of the grid frequency.
"E. Day Analys." screen menu.
6.
Screen 6.1
Indicator of the energy generated during the day.
"E. Tot. Analys." screen menu.
7.
Screen 7.1
Indicator of the energy that has been generated
since the start-up of the inverter.
"Time ON" screen menu.
8.
Screen 8.1
Indicator of the time that the inverter has been in
operation since its start-up.
"General Settings" screen menu.
9.
Screen 9.1
"Info.System" Inverter information.
Screen 9.1.1 Firmware version of the device.
Continued 9.2.3.
Screen 9.1.2 SSID. Identifying the WiFi network.
Screen 9.1.3 FW version (II).
Screen 9.2
Fault Info.
Screen 9.3
RSSI. Indicator of the intensity of the WiFi signal
received (Received Signal Strength Indicator).
Screen 9.4
WiFi conn.
Screen 9.4.1 ESP BT. Bluetooth connection mode.
Screen 9.4.2 ESP WIFI. WiFi connection mode.
Screen 9.5
Reset WiFi. Reset the WiFi settings.
Screen 9.6
WiFi update. Update the unit via WiFi.
Screen 9.7
Safety UNE 217002.
Screen 9.7.1 50 Hz Default.
Screen 9.7.2 60 Hz Default.
Screen 9.7.3 VDE4105.
Screen 9.7.4 ES:UNE217002.
Screen 9.7.5 EN50549.
Screen 9.7.6 Vietnam.
Screen 9.7.7 India.
Screen 9.7.8 Philippines.
Screen 9.7.9 Sri Lanka.
86
Screen 9.7.10 Italy.
Screen 9.7.11 EN50549(CZ).
Screen 9.7.12 EN50549(TR).
Screen 9.7.13 EN50549(IE).
Screen 9.7.14 EN50549(SE).
Screen 9.7.15 EN50549(PL).
Screen 9.7.16 EN50549(HR).
Screen 9.7.17 Belgium.
Screen 9.7.18 South Africa.
Screen 9.7.19 G98.
Screen 9.7.20 Austria.
Screen 9.8
Adj. Work. Mode. Configuration of the work
mode.
Screen 9.9
Batt. Ident. Battery manufacturer configuration
Screen 9.10
P. Limit ON/OFF. Function to limit injection to
the grid. Zero injection function.
After changing the work mode, this option must be
confirmed.
The following parameter must be set for the zero injection
function.
Screen 9.11
Export. Percentage injected into the grid. 0% for
zero injection and 100% to dump surpluses into the grid.
Screen 9.12
Pow. factor. Power factor.
Screen 9.13
CT ratio. Current transformer (CT) transforma-
tion ratio. It is set automatically when the meter is detected.
Screen 9.14
Modbus Addr.
Screen 9.15
Date/Time.
Screen 9.16
Language.
Screen 9.16.1 Spanish Language.
Screen 9.16.2 Polish language.
Screen 9.16.3 Czech Language.
Screen 9.16.4 English Language.
"Advanced Config." screen menu. Password "1111".
10.
Screen 10.1
Grid Isolating Switch. If enabled, the inverter will
automatically switch to off-grid mode to ensure back-up loads
when the grid is abnormal or off.
Screen 10.2
Grid Disconn. If it is enabled, it reduces the
switching sensitivity of On/Off-Grid if the grid is unstable.
Screen 10.3
Reconnection T. Reconnection time when there
is no grid and there is an overload in the back-up line.
Screen 10.4
NON-PEAK mode. Function to enable the non-
peak consumption option.
Screen 10.5
Grid Pmax kVA. Power limit for non-peaks.
Screen 10.6
Pr. SOC On-Gr. Function to enable the SOC
protection for the On-Grid battery.
Screen 10.7
On-Grid DOD. Configuration of the On-Grid
protection DOD.
Screen 10.8
Pr. SOC Off-Gr. Function to enable the SOC
protection for the Off-Grid battery.
Screen 10.9
Off-Grid DOD. Configuration of the Off-Grid
protection DOD.
Screen 10.10
Off-Grid V. Output voltage in Off-Grid.
Screen 10.11
Off-Grid F. Output frequency in Off-Grid.
SALICRU

Advertisement

Chapters

Table of Contents
loading

Table of Contents