Guide To Configure The Inverter Using - Salicru EQUINOX EQX2 4002-HT User Manual

Three-phase hybrid solar inverters connected to the grid
Table of Contents

Advertisement

Available languages

Available languages

7.5. GUIDE TO CONFIGURE THE INVERTER
USING THE DISPLAY.
The parameters that must be configured for start-up are as
follows:
BLUETOOTH/WIFI COMMUNICATION.
Communications are set to bluetooth by default, so you
ˆ
must change to WiFi if you want to connect the equip-
ment to the EQX-sun app. To do so, access the "General
Config." menu and then the "WiFi Conn." parameter.
WORK MODE.
To select the required work mode, access the "General
ˆ
Config." menu and then the "Adj. Work. Mode" param-
eter.
BATTERY TYPE.
If there are batteries, enter the type used. To do so,
ˆ
access the "General Config." menu and then the "Batt.
Ident." parameter. There are two types of compatible
battery manufacturers:
EQX_BATT: Salicru.
Pylon_HV: PylonTech.
CT TRANSFORMERS.
The CT ratio is configured automatically when the meter
ˆ
is detected. To configure it manually, access the "General
Config." menu and the "CT Ratio" parameter.
DEPTH OF DISCHARGE (DOD).
The DOD limits battery discharge to a minimum SOC (State
ˆ
of Charge) to protect the battery. For example, a DOD value
of 90% indicates that it will prevent further discharge
when the battery reaches 10% capacity. To configure it,
you must access the "Advanced Config." menu. Enter the
password "1111" and then configure the "Pr. SOC On-Gr."
and "Pr. SOC Off-Gr." parameters and enable the "On-Grid
DOD" and "Off-Grid DOD" parameters.
92
Options.
ZERO INJECTION.
Access the "General Config." menu to configure the
ˆ
following parameters:
In order not to dump the surpluses into the grid,
enable Zero Injection via the "P. Limit" parameter.
Set the "Export" parameter to 0%.
PEAKLOAD SHIFTING.
To enable the PeakLoad Shifting function, you must
ˆ
access the "Advanced Config." menu with the password
"1111", and enable the "NON-PEAK mode" parameter
and set the Pmax power limit with the "Grid Pmax. kVA"
parameter.
ECONOMY MODE PROFILE.
In order to use Economy mode, you must set a charge and
ˆ
discharge profile. To do so, access the "Advanced Config."
menu and set the following parameters for charging:
"Charging Start T.": Start time for charging
"Charging End T.": End time for charging
"Charging P. Lim.": Charging power limit
Access the "Advanced Config." menu and configure the
ˆ
following parameters for discharging:
"Discharging Start T.: Start time for discharging
"Discharging End T.": End time for discharging
"Discharging P. Lim.": Discharging power limit
SALICRU

Advertisement

Chapters

Table of Contents
loading

Table of Contents